Is your generator running, but your digital clock is gaining time, or your UPS keeps rejecting the power? These are classic signs of incorrect frequency. While most generator owners know how to check voltage, frequency (Hz) often goes unnoticed until sensitive electronics fail to operate. Low frequency can cause motors to overheat and lights to flicker, creating a frustrating power environment during an outage.
The mechanism behind this is mechanical. Unlike voltage, which is managed by an Automatic Voltage Regulator (AVR), the frequency of a generator is directly locked to the engine speed (RPM). To increase the frequency, you must physically increase the engine's Revolutions Per Minute. This direct physical coupling means that a slow engine guarantees low frequency output.
In this guide, we will break down the physics of the RPM-Hz relationship and provide a step-by-step tutorial for adjusting portable units. We will also cover critical safety warnings. Increasing the frequency often causes a spike in voltage, so monitoring both simultaneously is essential to prevent damaging your appliances.
RPM Equals Frequency: For a standard 2-pole portable generator, 3600 RPM = 60 Hz. For a 4-pole industrial unit, 1800 RPM = 60 Hz.
The "Droop" Factor: Always set no-load frequency slightly high (61–62 Hz) to accommodate the natural RPM drop when loads are applied.
Diagnostics First: Before adjusting the governor, ensure the engine isn't "hunting" (surging) due to a dirty carburetor or fuel issue.
Voltage Correlation: On most portable units, increasing RPM will also spike voltage. You may need to re-tune the Automatic Voltage Regulator (AVR) after fixing frequency.
To safely adjust your generator, you must first understand the "authority" that physics holds over your machine. You cannot cheat the relationship between engine speed and electrical output. This mechanical lock is what defines Alternating Current (AC) generation.
There is an industrial standard formula that dictates exactly what your engine must do to produce the correct electricity. It is defined as:
f = (N × P) / 120
In this equation:
f stands for Frequency (measured in Hz).
N represents the Engine Speed (measured in RPM).
P is the Number of Poles in the alternator.
This formula reveals that frequency is purely a function of how fast the magnetic field passes over the copper coils. If you need to calculate the target frequency of a generator based on your specific engine type, this formula is your starting point. It proves that if "P" (poles) is fixed, "N" (speed) is the only variable you can change to fix "f" (frequency).
Because the number of poles is a fixed physical attribute of your generator's alternator, the required engine speed is also fixed. You cannot run a generator at "any" speed; it must be precise.
2-Pole Generators (Most Portables): These are the standard gas units found in garages. They must maintain 3600 RPM to produce 60 Hz. If you are in a region using 50 Hz, they must run at 3000 RPM.
4-Pole Generators (Industrial/Diesel): These are larger, heavier, and quieter. They must maintain 1800 RPM to produce 60 Hz (or 1500 RPM for 50 Hz).
It is vital to confirm your 4 pole generator speed requirements before touching the throttle. If you mistakenly try to force a 4-pole generator to run at 3600 RPM, you will cause catastrophic mechanical failure.
| Generator Type | Alternator Poles | Target Frequency (Hz) | Required RPM |
|---|---|---|---|
| Portable (Gasoline) | 2 | 60 | 3600 |
| Portable (Gasoline) | 2 | 50 | 3000 |
| Industrial (Diesel) | 4 | 60 | 1800 |
| Industrial (Diesel) | 4 | 50 | 1500 |
A common misconception is that opening the throttle simply "speeds up" the engine. In a generator context, it is helpful to think of this like riding a bicycle up a hill.
Imagine you must maintain a perfect speed of 15 mph (representing 60 Hz). When you hit a hill (Electrical Load), the bike naturally slows down. To maintain 15 mph, you must pedal harder (add more fuel). The governor on a generator does exactly this: it opens the throttle not to go faster than 3600 RPM, but to maintain 3600 RPM against the resistance of the load.
Before you pick up a screwdriver, determine your generator’s pole count. If it is a small portable gas unit, it is almost certainly a 2-pole machine requiring 3600 RPM. If it is a large diesel standby unit, it is likely a 4-pole machine. Knowing this target prevents you from over-speeding the engine and throwing a connecting rod.
Many users immediately attempt a Generator frequency adjustment when they hear the engine running poorly. However, adjusting the governor screw on a sick engine is a mistake. You must distinguish between a calibration issue and a maintenance issue.
You can diagnose the root cause by listening to the engine and watching the frequency meter:
Consistently Low Hz: The engine runs smoothly and consistently, but the frequency reads 55 Hz or 56 Hz. It does not fluctuate wildy; it is just slow. Solution: This is a governor adjustment issue. The spring tension has likely relaxed over time.
Fluctuating Hz (Hunting/Surging): The engine revs up and down rhythmically (e.g., jumping from 58 Hz to 63 Hz and back). Solution: This is a fuel system issue. The pilot jet is likely clogged, causing a lean condition.
If your generator is "hunting," turning the governor screw will not fix it. In fact, it will make the surging worse. A dirty carburetor prevents the engine from getting a steady stream of fuel. The governor senses the RPM drop, snaps the throttle open, and the engine revs up. Then it overshoots, and the governor closes the throttle. This cycle repeats.
If you see hunting, put the screwdriver down. You need to clean the carburetor or add a strong fuel system cleaner. Only adjust the frequency once the engine idle is smooth.
It is also crucial to understand the role of the Automatic Voltage Regulator (AVR). The AVR controls voltage (120V/240V), not frequency. If your frequency is low (e.g., 55 Hz), adjusting the brass screw on the AVR will do absolutely nothing to fix the Hz. It will only change the voltage. You must address the engine speed first.
Once you have confirmed the engine is healthy (smooth running) but simply slow, you can proceed with the adjustment. This process applies to most mechanical governor systems found on portable generators.
You do not need expensive equipment, but you do need a way to measure the output.
1. Frequency Multimeter: Ideally a digital multimeter with a "Hz" setting.
2. Screwdriver/Pliers: To adjust the governor screw.
3. Safety Gear: Gloves and eye protection, as the engine will be running.
If you do not have a multimeter, you can use the "Analog Clock" method described later in this section.
You need to find the Governor Throttle Screw. This is not the idle mixture screw on the carburetor itself. Look for the governor arm—a metal lever connected to the carburetor throttle by a metal rod and a spring.
There will be a long threaded screw that puts tension on a spring connected to this arm. It is often marked with yellow paint from the factory. This screw controls the target RPM.
Warm Up: Start the generator and let it run for 5 to 10 minutes. The engine needs to reach full operating temperature so the metal components expand and the oil circulates. A cold adjustment will be inaccurate.
Measure Baseline: Plug your multimeter into one of the 120V outlets. Ensure there are no appliances connected (No Load condition). Note the current Hz.
Adjust: Locate the governor screw. To increase frequency, you typically turn the screw clockwise. This tightens the spring, pulling the governor arm to a higher speed setting. Turn it slowly while watching the meter.
Target Setting (Crucial): Do not stop at exactly 60.0 Hz. Aim for a target of 61.0 to 62.0 Hz under no-load conditions.
You might wonder why we aim for 61 or 62 Hz. This is to account for "Governor Droop." Mechanical governors are not perfect. When you apply a heavy load (like a heater or a saw), the engine speed will naturally dip slightly before the governor catches it.
If you set the baseline exactly at 60 Hz, the unit might drop to 58 Hz under load, which is low enough to damage some equipment. By setting the no-load baseline to 61–62 Hz, you ensure that when the generator is working hard, it settles right into the "sweet spot" of 60 Hz.
If you are in an emergency and do not have a multimeter, you can use an old-school analog electric clock (the kind with a sweep second hand that plugs into the wall).
Plug the clock into the generator.
Use a stopwatch (or your phone) to time the second hand for exactly one minute.
If the second hand completes a full rotation in less than 60 seconds, the frequency is too high.
If it takes more than 60 seconds to complete a rotation, the frequency is low.
Adjust the screw until the clock keeps perfect time with your stopwatch. This method is surprisingly accurate because these clocks rely directly on the 60 Hz cycle to keep time.
Changing the RPM does not just change the frequency; it affects the entire power quality profile. You must verify the safety of the output before plugging in sensitive electronics.
On simple portable generators, there is a physical link between speed and voltage. As the rotor spins faster (increasing Hz), the magnetic flux density changes, often driving the voltage up.
After you have successfully increased the frequency to 60 Hz (or 62 Hz no-load), check your voltage. It is possible that your voltage has spiked to 130V or higher. Voltage this high can blow out light bulbs and damage surge protectors.
If the voltage is unsafe (typically above 127V):
1. Locate the Automatic Voltage Regulator (AVR) on the end of the generator head (usually a kidney-shaped component).
2. Find the small brass potentiometer screw on the AVR (often hidden under blue potting material).
3. Turn this screw counter-clockwise to lower the voltage back to a safe range (120V–124V) while the frequency remains at your new target.
The final step is to prove the generator can hold the frequency. Apply a 50% load, such as two 1500W space heaters. Watch the frequency meter.
The frequency should drop from your 62 Hz baseline but should stay above 58.5 Hz. If it drops drastically (e.g., to 55 Hz), the engine may be underpowered, or the governor spring may be fatigued and need replacement.
If you are managing a large industrial generator rather than a portable unit, the rules change. Commercial systems use different control logic.
High-end industrial generators often use "Isochronous" electronic governors. Unlike mechanical springs, these computer-controlled systems maintain exactly 60.0 Hz regardless of the load. They do not experience "droop." If you are adjusting one of these, you are likely changing parameters in a software controller rather than turning a screw.
For generators connected to the utility grid (Infinite Bus), the physics of adjustment are fundamentally different. If your generator is synchronized with the grid, increasing the throttle does not increase frequency.
Because the grid is infinitely stronger than your generator, the frequency is locked by the utility. Opening the throttle in this scenario increases the Real Power (kW) output and changes the torque angle. You are essentially pushing harder against an immovable wall. Do not attempt to adjust frequency on a grid-tied unit manually; you will only shift the power factor and load distribution.
Owners of inverter generators (like the Honda EU series) should note that engine speed is decoupled from output frequency. These units generate AC, convert it to DC, and then invert it back to clean AC.
If an inverter generator has low frequency, it indicates an electronic failure in the inverter module. Revving the engine will not change the output Hz. These units require component replacement, not adjustment.
Increasing the frequency of a generator is purely an exercise in RPM management. Whether you are dealing with a 2-pole portable unit or checking 4 pole generator speed, the rule remains the same: the engine must spin faster to increase the Hz.
Remember the critical relationship: Low Hz indicates Low RPM. However, correcting this low frequency can inadvertently cause a voltage spike. Always verify both metrics after any adjustment. If you find that the mechanical governor cannot maintain frequency within a safe range (+/- 3%) under load even after adjustment, it is likely time to evaluate replacing the governor spring or upgrading to a more precise electronic governing system.
A: No. Direct Current (DC) has a frequency of 0 Hz. If you are measuring frequency on a DC output, you are likely reading "ripple" or noise from the commutation process. Frequency is a property of Alternating Current (AC) only, representing the number of times the current reverses direction per second.
A: This is called "Governor Droop." As the load increases, the engine encounters magnetic resistance, similar to riding a bike uphill. A healthy generator should not drop below 58 Hz. If it drops lower, your no-load frequency should be adjusted higher (up to 62 Hz) or the generator is overloaded.
A: Slightly high frequency (61–62 Hz) is generally safe for most electronics and resistive loads like heaters. However, low frequency (under 57 Hz) is highly damaging to inductive loads like motors and compressors (refrigerators, air conditioners), causing them to run hot and eventually burn out.
A: Hunting is when the generator engine revs up and down rhythmically. This causes wild frequency fluctuations (e.g., 55–65 Hz). This is usually caused by a dirty carburetor or fuel obstruction, not a misadjusted governor screw. You must clean the fuel system to fix this before attempting any frequency adjustments.